SPECIFICATIONS OF DETECTORS
SMOKE DETECTOR
HEAT DETECTOR
MULTI DETECTOR
Detector Type | : | Dual-Optical | Thermal Differential/ Thermal maximum | Optical/Thermal | |
Operating Voltage | : | 15 V DC-33 V DC | 15 V DC-33 V DC | 15 V DC . . . 33 V DC | |
Current Consumption | : | < 0.55 mA | < 0.55 mA | < 0.55 mA | |
Protection Category | : | IP 40, IP 43 with MSF 400 | IP 40, IP 43 with MSF 400 | IP 40, IP 43 with MSF 400 | |
Permissible Operating Temperature | : | -20 °C . . . +65 °C | -20 °C . . . +50 °C | -20 °C . . . +50 °C | |
Monitoring Area | : | max. 120 m² | max. 40 m² | max. 120 m² | |
Maximum Installation Height
| : | 16 m | 7.5 m | 16 m |
Specifications of Detectors
BEAM DETECTOR
MANUAL CALL POINT
Current (alarm) | : | Receiver: 60 mA, Transmitter: 20 mA | Operating voltage | : | 10 V DC to 33 V DC |
Current (standby) | : | Receiver: 45 mA, Transmitter: 20 mA | Current consumption | : | 0.4 mA |
Voltage (operating) | : | 18 VDC to 32 VDC | Type H (outdoor use) | : | -25 °C to +70 °C |
Temperature (ambient) | : | -22°F to +130°F (-30°C to +54°C) | Type G (indoor use) | : | -10 °C to +55 °C |
Dimensions (H x W x D) | : | 7 in. x 5.5 in. x 5.5 in. | Dimensions (W x H x D) | : | 135 x 135 x 36 mm |
Transmission Range | : | 30 ft (9 m) to 350 ft (107 m) | Weight | : | Approx. 400 g
|
Voltage consumption | : | 9V to 12V |
Starting current | : | 150 mA |
In standby | : | 90 mA to 130 mA |
With alarm | : | 125 mA to 150 mA |
Permissible temperature range | : | -20 °C to +60 °C |
Maximum pipe length | : | 50m |
ASPIRATION SMOKE DETECTOR
FAP-1200 PANEL features:
- Easy upgrade to 2 loops by second LSN 0300 A module
- Connection of up to 254 elements (127 per loop)
- Remote operation by up to 3 Remote Keypads (via CAN or Ethernet)
- Auto-detection of modules and Plug-in of modules during operation
- Serial interface to Bosch Voice Evacuation System (EVAC)
Operating voltage | : | 20 V DC to 30 V DC |
Display element | : | 14.5 cm (5.7”) multi-color TFT display |
Operating element | : | Touch screen |
Interfaces | : | • Ethernet • USB • RS232 |
Dimensions (H x W x D) | : | 638 mm x 440 mm x 149 mm (25.1 x 17.2 x 5.87 inch) |
Weight | : | Approx. 20 kg (44 lb) |
Permissible operating temperature | : | -5 °C to 50 °C |
FAP-5000 PANEL
With its modular design, the FPA-5000 Fire Panel is easily adapted to local circumstances and Regulations. The fire panel is available with two different housings. All housings can be extended with various additional housings. All messages are shown on the display. Enables adaptation to country-specific circumstances. The panels can be networked with one another and with the remote keypad Connection to a building management system is possible |
REMOTE KEYPAD EN FMR-5000-C-13
Operating voltage | 12 V DC to 30 V DC |
Max. current consumption · Standby
· Alarm |
140 mA @ 24 V DC 230 mA @ 24 V DC |
Max. resistance | 18 Ω |
Max. cable length · CAN networking
· Ethernet/IP networking with fiber |
1000 m depending on configuration, topology and cable type 24 to 40 km |
Features
– Convenient remote operation of fire panel identical to Panel Controller
– Multi-color display
– 11 LEDs displaying the operating status of the system
– Surface and flush mounting
– Display element: 14.5 cm (5.7″) multi-color TFT display with 320 x 240 pixels
– Operating elements: Touch screen with 127.5 mm x 170 mm active surface
– Interfaces: CAN, ETH, USB, RS232